Q: Please define turndown ratio and tell what the advantages are for a higher turn down?

A: Turndown ratio is the ratio of maximum fuel input rate to minimum fuel rate of a variable input burner. Traditionally burners on firetube boilers operate in the 4:1 turndown ratio range depending on fuel and size. Advantages of high turndown burners include: Reduction of standby losses Limiting thermal cycling Saves wear and tear of burner components Disadvantages include: Initial cost and complexity Requires more maintenance Limitations of Boiler/burner system The limitations include fuel/air mixing requirements, material temperature issues, flame shape characteristics, flow control limitations and pressure vessel limitations.